fn main raise {
let device = @bac.Device::new(4201, "office-floor-control", 999U)
let setpoint = @bac.ObjectId::new(2, 1)
let temperature = @bac.ObjectId::new(0, 1)
device.add_point(
setpoint,
"room-setpoint",
Analog,
Real(19.0F),
commandable=true,
units=62U,
)
device.add_point(
temperature,
"room-temperature",
Analog,
Real(20.2F),
units=62U,
)
let server = @bac.Server::new(device)
let client = @bac.Client::new()
let present : @bac.PropertyRef = {
object: setpoint,
property: 85U,
index: None,
}
@support.write(server, client, setpoint, Real(21.0F), 16, 0UL)
@support.write(server, client, setpoint, Real(23.0F), 8, 1UL)
@support.assert_real(@support.read(server, client, present, 2UL), 23.0F)
@support.write(server, client, setpoint, Real(26.0F), 1, 3UL)
@support.assert_real(@support.read(server, client, present, 4UL), 26.0F)
@support.write(server, client, setpoint, Null, 1, 5UL)
@support.assert_real(@support.read(server, client, present, 6UL), 23.0F)
@support.write(server, client, setpoint, Null, 8, 7UL)
@support.assert_real(@support.read(server, client, present, 8UL), 21.0F)
@support.write(server, client, setpoint, Null, 16, 9UL)
@support.assert_real(@support.read(server, client, present, 10UL), 19.0F)
assert_eq(device.active_priority(setpoint), None)
let slots = @support.read(
server,
client,
{ object: setpoint, property: 87U, index: Some(0U), },
11UL,
)
assert_eq(
@bac.encode_tags(slots),
@bac.encode_tags([Application(Unsigned(16U))]),
)
device.update(temperature, 85U, Real(21.3F))
@support.assert_real(
@support.read(
server,
client,
{ object: temperature, property: 85U, index: None, },
12UL,
),
21.3F,
)
assert_eq(client.pending_count(), 0)
println(
"HVAC: schedule 16, operator 8, override 1; relinquish restores lower slots then default; sensor read passed",
)
}